Anasayfa / Ürünlerimiz / Microtest 71107120 Single-Phase Power Meter
Product Description:
MICROTEST’s single phase power meter 7110/7120 has the wave crest factor of the input current as CF3/CF9 and able to measure all the values within measuring ranges. They have the fastest auto-shift speed amongst other testers of the same level, and the measuring span can be locked on rapidly to perform accurate power consumption analysis. The measuring range of both PM7110/7120 are 0.001W~16KW, and they are able to measure AC power consumption containing DC and obtain power factors with higher accuracy while analyzing the current signals from devices with asymmetrical positive and negative waveforms. All the electronic devices on the market must comply with EU requirements for standby power consumption, and the manufacturers are making their effort to lower it as best as they can. PM7110/7120 are able to help the manufacturers to analyze power and energy consumption precisely and perform long-hours survey with a PC.
AC / DC Dual amp / watt-hour meter
Wide range 0.001W ~ 16KW
Connection software attached
Standby Power D.P.I. of 0.001W
With crest factor ratio display
Up to the 50 levels harmonic wave analysis capability
1000 sets of measurement data storage space
Product Specification:
Harmonics
Analysis base To achieved stable fundamental frequency analysis by voltage or current (non-inverter)
Frequency Range 45Hz ~ 440Hz
FFT Data Length 1024
FFT Data Format 32 bits
Measurement Projects 1-50 THD, 1-50 level voltage and current V [n], A [n] 1-50 level voltage and current distortion percentage V [n%], A [n%] 1-50 level watts W [n] 1-50 level watts distortion percentage Watt W [n%] 1-50 level voltage and current angle DEG [n] Vrms,Irms,Watt, PF
Specification
Model Name 7110 7120
Power Supply Voltage 100 ~ 240Vac
Frequency 50/60Hz
Display
Seven-segment display
Interface RS232 RS232+GPIB
Flash Memory 6 Sets
Environment Temperature:23℃±5℃ Humidity: 20%~80%
Dimension (W*H*D) 335x103x335 mm
Weight 1.85 Kg
Measurement bandwidth
DC 15Hz ~ 10KHz DC 15Hz ~ 100KHz
Harmonic (Option) Yes/NA Yes/NA
Model 7110-10K-HARM
7110-10K
7120-100K-HARM
7120-100K
Fixture F71201 TEST BOX
Measurement Data
Model 7110 7120
Frequency Measurement Mode To achieved stable base frequency measurement(variation less than 1%)by voltage or current (non-inverter)
Frequency Range DC,15Hz~10KHz DC,15Hz~100KHz
Data Length Dual 4096×16 RAM for voltage & current
ADC Resolution 16 bits
Sampling Rate AC 50Hz / 60Hz basic sampling rate 100 KSPS / 120 KSPS
Arithmetic Precision Watt/VRMS/IRMS/MEAN/PF/Deg/Line filter 32bits
Frequency Filter 500Hz cut off, digital chip filter based on 25MHz
Signal Filter 500Hz -3db digital filter based on Butterworth
50Hz -0.03% reading, 60Hz -0.05% reading
Frequency Acquisition Mode Voltage / current 100MHz baseband digital dynamic meter chip
Phase Lead Detection Subject to the current, analog / digital hybrid detecting (error less than 5 degrees)
Range
Current (fixed / auto) 0.01A、0.03A、0.1A、0.3A、1A、3A、10A、20A
Voltage (fixed / auto) 10V、30V、100V、300V、600V
RMS/MEAN Mode Voltage & Current Accuracy (23℃±5℃)
>=15 Hz, f ≦ 45Hz ±(0.1% of reading + 0.4% of range)
>45 Hz, ≦ 66 Hz ±(0.1% of reading + 0.1 % of range)
>66 Hz, ≦ 1 kHz ±(0.1% of reading + 0.2 % of range)
>1 kHz, ≦ 10 kHz ±(0.07*f % of reading + 0.3% of range)
>10 kHz, ≦100 kHz ±(0.5% of reading + 0.5% of range) ±[{0.04×(f–10)}% of reading]
F unit is 1KHz
When the L-FILTER sets as ON:45Hz~66Hz frequency range allowable error-0.03 %~-0.05 of reading
When the AC is measured, if the fundamental frequency exceeds 200Hz, the F-Filter is required to be turned off in order to measure the most accurate value
**When the frequency range is more than 10KHz, the 7120 starts to support
DC Mode Voltage & Current Accuracy (23℃±5℃)
10V~600V ±0.2% reading ± 0.2% of range 0.01A ~20A ±{(0.2)% of reading + 0.2 % of range}±offset
To add up the OFFSET errors of various files during measuring the DC current
Power (W) Accuracy (23℃±5℃)
AC power ranges (Auto or Manual)(40 ranges) range up to 16KW
Maximum Power (W) value is determined by the highest range of voltage profile
DC ±0.2% reading ± 0.5% of range
15 Hz≦f
45 Hz≦f≦66 Hz ±(0.1% of reading + 0.1 % of range)
66 Hz
1 kHz
10 kHz
Incidental allowable error conditions
Signal filter error (AC)
Frequencies between 45 to 66 Hz: Add 0.3% of reading
Frequency at 45 to 66 Hz: Add 1% of reading beyond
CF9 error (DC) Add range tolerance * 3
Accuracy effect of the phase error of the power
When the power factor PF is 0, the error range of Watt is
Situation 1: for 45 Hz
Situation 2: for 45 Hz>f or f >66 Hz
Add ±{(3.5 + 0.5 × f)% of VA} for up to 100 kHz as reference data
The unit for frequency f is kHz.
When the power factor is 0 < PF ≦error range
When 0
for 45 Hz≦f≦66 Hz. Add ± power reading *{tan(θ)*(0.5)}%
for f < 45 Hz, f >66 Hz. Add ± power reading *{ tanθ* (0.5×f+0.2) }%
Error within 12 months Add ±(0.5% of reading)
Parameters Measurement Range
Vrms 0.1V ~ 600V PF 0.000 ~ ±1.000
Vdc 0.1V ~ 600V Deg -180°~ +180°
Irms 0.1mA ~ 20A THD 0.01% ~ 99.99%
Idc 0.1mA ~ 20A Hz 15Hz ~100kHz
W 0.01W ~16KW
Applications
The measurements are utilized in environmental monitors, energy saving lamps, exchangeable power supplies, transformers, uninterruptible power systems, power tools, 3C electronic products, and home appliances, etc.